Phone

    00852-6915 1330

Some Suggestions about Protecting Transformers

  • Contents

 

This article will be divided into three parts--individual transformer , parallel transformer and redundancy requirements for bulk power transformers.

 

 


Catalog

 

I. Individual Transformer

II. Parallel Transformer

III. Redundancy Requirements for Bulk Power Transformers

FAQ

 


I. Individual Transformer

 

Just see the following picture, it includes the protection for banks where fuses are used on the primary. Overall differential protection may be applied by using CTs in the transformer primary bushings for larger or important banks. The common connection is shown with delta on the source (primary) side and wye-grounded on the secondary side. Other possible connections: delta–delta, wye–wye, or primary-wye– secondary-delta.

Transformer protection without primary-side circuit breaker

Figure 1 – Transformer protection without primary-side circuit breaker

 

About the analysis of power circuit, you can see the article: Analysis of Switching Power Supply Principle

 

Note: Secondary circuits should have 51 and 51N relays. Therefore, transformer secondary breaker and relays may be omitted unless another source connects to the secondary bus. 51N relay can be omitted with 51G available.

 

For transformer banks with primary breakers, the protection is summarized in Figure 2.

 

Relay 51G provides backup protection for secondary bus and feeder faults and must be time-coordinated, with other ground relays protecting the various feeder circuits on the secondary bus. Similarly, phase relays 51 must be coordinated with the phase relays on the feeders. The common connection is shown with delta on the source (primary) side and wye-grounded on the secondary side. Other possible connections: delta–delta, wye–wye, primary-wye– secondary-delta, three-winding, or autotransformer.

 

Transformer protection with primary-side circuit breaker

Figure 2 – Transformer protection with primary-side circuit breaker

 

"52S may be omitted in some applications requiring 151G to coordinate with and trip the secondary circuit devices if used."


II. Parallel Transformer

 

The protection for transformer banks where the secondaries are connected together by a bus tie breaker is summarized in the following picture(a,b,c).

 

The arrangement shown is typical for large- or critical-load substations, especially for industrial plants. The loads are supplied from separate buses that are connected together by a bus tiebreaker (52T) that may be operated either normally closed (NC) or normally open (NO).

 

Single line diagram of transformer and secondary bus protection for a typical double-source supply with secondary tie and breaker

Figure 3a – Single line diagram of transformer and secondary bus protection for a typical double-source supply with secondary tie and breaker

 

If you operated NO, the protection of the first picture and second is applicable. If operated with 52T NC, the protection of the first picture and second is applicable with the secondary side modified.

Secondary protection with high-side fuses

Figure 3b – Secondary protection with high-side fuses

With the bus tiebreaker closed, there is a possibility for the interchange of power between the two sources. Here, current flows from one source through its transformer, the secondary buses, and back through the other transformer to the second source. Generally, this is neither desirable nor permitted.

 

"To prevent this operation, directional time–overcurrent relays (67, 67N) are applied to each transformer."

 

Secondary protection with high-side breaker

Figure 3c – Secondary protection with high-side breaker

The single-line connections are shown in Figure 3b and Figure 3c, with complete three-line connections in the following figure.

 

Note: They operate only for fault current that flows into the transformer and trip the secondary breaker (52–1 or 52–2). This is also important in removing a secondary fault source for faults in the transformer bank. The phase relays (67) can be set on a low of the minimum tap.

 

Load current certainly flows through the relay, but normally not in the operating direction. The low tap continuous rating must not be exceeded by increasing the maximum load current. The 67-time setting must coordinate with the protection on the transformer primary. When used, the ground relay can be set on minimum setting and time, because coordination is not necessary.

 

Three-line connections for reverse-phase and partial differential backup protection

Figure 4 – Three-line connections for reverse-phase and partial differential backup protection

The inverse-time–overcurrent relays (51, 51N) provide bus protection and backup protection for the feeder circuits. These relays trip both 52–1 (or 52–2) and 52T. This is a partial differential connection and these units must be time-coordinated with the protection on the several feeders that are connected to the bus.

 

"Only two-phase relays are required, but the third relay (shown optionally in Figure 4) provides additional redundancy. When a ground differential is used, as illustrated in Figure 3c, 67N and 51N are omitted."

 

Ground-fault backup is provided by 51G, 151G, and 251G inverse-time overcurrent relays (Figure 3abc). Relay 251G provides bus ground-fault protection and backup for the feeder circuit ground relays. It must be time- coordinated with these. It trips the bus tie 52T, as the fault could be either on the bus or on the associated feeders.

 

If the fault continues to exist with the bus tie open, relay 151G trips breaker 52–1 (or 52–2). Thus, 151G must coordinate with 251G. If the fault persists, it is between the secondary breaker, in the transformer winding, or in the grounding impedance.

 

Relay 51G set to coordinate with 151G is the last resort. It trips the high-side or primary breaker to remove the transformer from the service.

 


III. Redundancy Requirements for Bulk Power Transformers

 

When transformers are connected to bulk power systems, redundancy requirements for related protection need to be addressed. To provide the required redundancy, two separate differential schemes may be applied.

 

"Redundancy for transformer faults may also be obtained by a differential scheme and sudden pressure."

 

In such an application, the sudden pressure protection needs to be supplied with additional protection for faults on the transformer bushings and leads, as sudden pressure devices will not respond to faults in these areas. Redundant schemes for disconnecting the transformer from the system when a high-side breaker is not applied can be obtained by using various combinations of the methods. Take an example, two separate transfer trip systems may be applied although they are expensive. A cheaper alternative is to combine a transfer trip scheme and a faulty switch. It may be possible to delay closing the fault switch for a few cycles to allow time for the transfer trip scheme, provided it is operational, to de-energize the failed transformer before the closing of the fault switch. This would spare the power system from being subject to a solid fault when the fault switch closes, whenever the transfer trip scheme works properly.

 

When a high-side breaker is applied and it fails to operate, breaker failure protection is required to enable isolation of a faulted transformer. The breaker failure scheme may require the application of a fault switch, transfer trip scheme, or a second interrupting device if other local breakers are not available to isolate the transformer.

 


FAQ

 

 

1. What is the use of transformer?

Transformers are employed for widely varying purposes; e.g., to reduce the voltage of conventional power circuits to operate low-voltage devices, such as doorbells and toy electric trains, and to raise the voltage from electric generators so that electric power can be transmitted over long distances.

 

2. What are the 3 types of transformers?

There are three primary types of voltage transformers (VT): electromagnetic, capacitor, and optical.

 

3. What is the basic principle of transformer?

A transformer consists of two electrically isolated coils and operates on Faraday's principal of “mutual induction”, in which an EMF is induced in the transformers secondary coil by the magnetic flux generated by the voltages and currents flowing in the primary coil winding.

 

4. Does a transformer convert AC to DC?

A transformer is built to transfer the energy from one circuit into another circuit by way of magnetic coupling. ... An alternating current creates a magnetic flux in the core on its way through the first winding, inducing the voltage in the others. It can convert high and low voltages, it cannot convert AC to DC.

 

5. What are the main parts of transformer?

There are three basic parts of a transformer:

a. an iron core which serves as a magnetic conductor,

b. a primary winding or coil of wire and.

c. a secondary winding or coil of wire.

 

6. What are the classification of transformer?

Depending upon the type of construction used, the transformers are classified into two categories viz.: (i) Core type, and (ii) Shell type. Depending upon the type of service, in the field of power system, they are classified as: (i) Power transformers, and (ii) Distribution transformers.

 

7. Can a transformer work on DC?

As mentioned before, transformers do not allow DC input to flow through. This is known as DC isolation. This is because a change in current cannot be generated by DC; meaning that there is no changing magnetic field to induce a voltage across the secondary component.

 

8. How do you convert a transformer?

This conversion is made by winding two separate conductors around a common iron core. Applying an alternating voltage to the primary conductor produces current which sets up a magnetic field around itself. This is known as mutual inductance.

 

9. What are two components of no load current in transformer?

The no-load current of a transformer consists of two components: The Magnetization Current iM is the current required to produce the flux in the transformer core. The Core-loss Current ih+e is the current required to make up for hysteresis and eddy current losses.

 

10. Which type of transformer core is most efficient?

SHELL CORE. The most popular and efficient transformer core is the SHELL CORE, as illustrated in figure (4). As shown, each layer of the core consists of E- and I-shaped sections of metal. These sections are butted together to form the laminations.

 

11. What is the power factor of transformer?

The power factor of a distribution transformer is between (0.75 to 0.80) when secondary is connected to u.p.f loads.

 

12. Why do we need Transformers?

Transformers help improve safety and efficiency of power systems by raising and lowering voltage levels as and when needed. They are used in a wide range of residential and industrial applications, primarily and perhaps most importantly in the distribution and regulation of power across long distances.

 

13. What is the difference between a step up transformer and a step down transformer?

A transformer that increases the voltage from primary to secondary (more secondary winding turns than primary winding turns) is called a step-up transformer. Conversely, a transformer designed to do just the opposite is called a step-down transformer.

 

14. Are transformers dangerous?

There is no established evidence that the exposure to magnetic fields from powerlines, substations, transformers or other electrical sources, regardless of the proximity, causes any health effects.

 

15. Why transformer rating is in kVA not in kW?

Copper losses (I²R) depends on current which passing through transformer winding while Iron losses or core losses or Insulation losses depends on Voltage. ... That's why the transformer rating may be expressed in VA or kVA, not in W or kW.



 

 

Kynix

Kynix was founded in 2008, specializing in the electronic components distribution business. We adhere to honesty and ethics as our business philosophy and have gradually established an excellent reputation and credibility in our international business. With the accurate quotation, excellent credit, reasonable price, reliable quality, fast delivery, and authentic service, we have won the praise of the majority of customers.

Join our mailing list!

Be the first to know about new products, special offers, and more.

Leave a Reply

We'd love to hear from you! Feel free to share your thoughts and comments below. Rest assured, your email address will remain private.

Name *
Email *
Captcha *
Rating:

Kynix

  • How to purchase

  • Order
  • Search & Inquiry
  • Shipping & Tracking
  • Payment Methods
  • Contact Us

  • Tel: 00852-6915 1330
  • Email: info@kynix.com
  • Follow Us

authentication

Kynix

© 2008-2026 kynix.com all rights reserved.